Qhov txawv ntawm tooj liab winding ua nyob rau hauv ib tug transformer, piv rau txhuas winding?
Nov 20, 2025
Tso lus
Aluminium yog dav siv thiab nws yog hloov tooj liab nyob rau hauv lub tshav pob ntawm hluav taws xob engineering. Nws conductivity yog me ntsis tsawg dua tooj liab tab sis nws zoo li pheej yig thiab yooj yim muaj.
Kev tiv thaiv tshwj xeeb tshwj xeeb ntawm Aluminium yog 1.64 npaug ntawm tooj liab
Yog li ntawd, siv aluminium winding nce lub zog poob.
Kev siv cov txhuas tus neeg xyuas pib ua rau txo qis ntawm 22%.
Txawm hais tias txhuas siv hluav taws xob pov tseg, nws yog siv rau nws lub teeb yuag thiab ACSR kis kab mob.
Cov no yog qhov sib txawv uas aluminium ua nrog tooj liab.
Technical Parameter rau 6kV, 10kV & 30kVA-2500kVA Nrog Tawm Circuit Qhuav Hom Transformer
| (KVA) Rated peev | Voltage kev sib xyaw | Connection Group Symbol | Tsis muaj -load Loss(W) | Load Loss (W) | Tsis muaj -load tam sim no (%) | Luv-circuit impedance(%) | ||||
| Lub zog hluav taws xob (KV) | Tapping ntau yam ntawm High Voltage | Tsawg Voltage (KV) | 130℃(B) (100 degree) | 155℃(F) (120 degree) | 180℃(H) (145 degree) | |||||
| 30 | 6 6.3 6.6 10 10.5 11 |
±2.5% ±5% |
0.4 | Dyn11 Yyn0 | 190 | 670 | 710 | 760 | 2 | 4 |
| 50 | 270 | 940 | 1000 | 1070 | 2 | |||||
| 80 | 370 | 1290 | 1380 | 1480 | 1.5 | |||||
| 100 | 400 | 1480 | 1570 | 1690 | 1.5 | |||||
| 125 | 470 | 1740 | 1850 | 1980 | 1.3 | |||||
| 160 | 540 | 2000 | 2130 | 2280 | 1.3 | |||||
| 200 | ±2X2.5% ±5% |
620 | 2370 | 2530 | 2710 | 1.1 | ||||
| 250 | 720 | 2590 | 2760 | 2960 | 1.1 | |||||
| 315 | 880 | 3270 | 3470 | 3730 | 1 | |||||
| 400 | 980 | 3750 | 3990 | 4280 | 1 | |||||
| 500 | 1150 | 4590 | 4880 | 5230 | 1 | |||||
| 630 | 1340 | 5530 | 5880 | 6290 | 0.85 | |||||
| 630 | 1300 | 5610 | 5960 | 6400 | 0.85 | 6 | ||||
| 800 | 1520 | 6550 | 6960 | 7460 | 0.85 | |||||
| 1000 | 1770 | 7650 | 8130 | 8760 | 0.85 | |||||
| 1250 | 2090 | 9100 | 9690 | 10300 | 0.85 | |||||
| 1600 | 2450 | 11000 | 11700 | 12500 | 0.85 | |||||
| 2000 | 3050 | 13600 | 14400 | 15500 | 0.7 | |||||
| 2500 | 3600 | 16100 | 17100 | 18400 | 0.7 | |||||
| 1600 | 2450 | 1220 | 12900 | 13900 | 0.85 | 8 | ||||
| 2000 | 3050 | 15000 | 15900 | 17100 | 0.7 | |||||
| 2500 | 3600 | 17700 | 18800 | 20200 | 0.7 | |||||
Technical Parameter rau 20kV 50kVA-2500kVA Nrog Tawm Circuit Court Qhuav Hom Transformer
| (KVA) Rated peev | Voltage kev sib xyaw | Connection Group Symbol | Tsis muaj -load Loss(W) | Load Loss (W) | Tsis muaj -load tam sim no (%) | Luv-circuit impedance(%) | ||||
| Lub zog hluav taws xob (KV) | Tapping ntau yam ntawm High Voltage | Tsawg Voltage (KV) | 130℃(B) (100 degree) | 155℃(F) (120 degree) | 180℃(H) (145 degree) | |||||
| 50 | 20 22 24 |
±2.5% ±5% |
0.4 | Dyn11 Yyn0 | 340 | 1160 | 1230 | 1310 | 2 | 5.0 |
| 100 | 540 | 1870 | 1990 | 2130 | 1.8 | |||||
| 160 | 670 | 2350 | 2470 | 3460 | 1.8 | |||||
| 200 | ±2X2.5% ±5% |
730 | 2770 | 2940 | 3140 | 1.8 | ||||
| 250 | 840 | 3220 | 3420 | 3660 | 1.8 | |||||
| 315 | 970 | 3850 | 4080 | 4360 | 1.8 | |||||
| 400 | 1150 | 4650 | 4840 | 5180 | 1.1 | |||||
| 500 | 1350 | 5460 | 5790 | 6190 | 1.1 | |||||
| 630 | 1530 | 6450 | 6840 | 7320 | 1 | |||||
| 800 | 1750 | 7790 | 8260 | 8840 | 1 | |||||
| 1000 | 2070 | 9220 | 9780 | 10400 | 0.85 | |||||
| 1250 | 2380 | 10800 | 11500 | 12300 | 0.85 | |||||
| 1600 | 2790 | 13000 | 13800 | 14800 | 0.85 | |||||
| 2000 | 3240 | 15400 | 16300 | 17500 | 0.7 | 8.0 | ||||
| 2500 | 3870 | 18200 | 19300 | 20700 | 0.7 | |||||
| 2000 | 3240 | 16800 | 17800 | 19100 | 0.7 | |||||
| 2500 | 3870 | 20000 | 21200 | 22700 | 0.7 | |||||
Technical Parameter rau 35kV 50kVA-2500kVA Nrog Tawm Circuit Court Qhuav Hom Transformer
| (KVA) Rated peev | Voltage kev sib xyaw | Connection Group Symbol | Tsis muaj -load Loss(W) | Load Loss (W) | Tsis muaj -load tam sim no (%) | Luv-circuit impedance(%) | ||||
| Lub zog hluav taws xob (KV) | Tapping ntau yam ntawm High Voltage | Tsawg Voltage (KV) | 130℃(B) (100 degree) | 155℃(F) (120 degree) | 180℃(H) (145 degree) | |||||
| 50 | 35 36 37 38.5 |
±2.5% ±5% |
0.4 | Dyn11 Yyn0 | 450 | 1340 | 1420 | 1520 | 2.3 | 6 |
| 100 | 630 | 1970 | 2090 | 2230 | 2 | |||||
| 160 | 0.79 | 2650 | 2810 | 3000 | 1.5 | |||||
| 200 | ±2X2.5% ±5% |
0.88 | 3130 | 3320 | 3550 | 1.5 | ||||
| 250 | 0.99 | 3580 | 3800 | 4060 | 1.3 | |||||
| 315 | 1170 | 4250 | 4510 | 4820 | 1.3 | |||||
| 400 | 1370 | 5100 | 5410 | 5790 | 1.1 | |||||
| 500 | 1520 | 6270 | 6650 | 7110 | 1.1 | |||||
| 630 | 1860 | 7250 | 7690 | 8230 | 1 | |||||
| 800 | 2160 | 8600 | 9120 | 9760 | 1 | |||||
| 1000 | 2430 | 9860 | 10400 | 11100 | 0.75 | |||||
| 1250 | 2830 | 12000 | 12700 | 13600 | 0.75 | |||||
| 1600 | 3240 | 14600 | 15400 | 16500 | 0.75 | |||||
| 2000 | 3820 | 17200 | 18200 | 19500 | 0.75 | |||||
| 2500 | 4450 | 20600 | 21800 | 23300 | 0.75 | |||||
Yog tias koj txaus siab rau peb cov khoom, thovhu rau peb los yog xa cov lus nug rau peb, peb yuav teb koj li ntawm ib teev.
Ntim & Shipping

Cov neeg siv khoom Case

Xa kev nug